The language of lightning, earthing and surge protection, in plain words.
46 terms used in standards, drawings and tender documents. Each definition follows the wording of IEC 62305, IS 3043 and IEC 61643, and links to the LPES solution or product where the term is put to work.
Air termination system
The part of an external lightning protection system that intercepts the strike: rods, catenary wires and meshed conductors placed by the rolling sphere, protection angle or mesh method.
Air termination productsAttached LPS
A lightning protection system fixed to the structure it protects. Most buildings use one. Separation distance must be kept or bonding provided.
Flat roof lightning protectionBack-up protection (SPD)
The fuse or breaker in series with a surge protective device. It must not exceed the maximum rating the SPD maker permits.
SPD assembliesBonding bar
A bar on which metal installations, external conductive parts, power and communication lines are bonded to the earthing system. Also called an earth bar.
Earth bars and terminalsClass of LPS
One of four classes, I to IV, that set the design values of a lightning protection system. Class I is the most demanding. The class comes from the risk assessment.
Lightning Risk AssessmentCoordinated SPD system
Surge protective devices selected and installed as one system so that each stage hands a reduced surge to the next, from the service entrance to the equipment.
Surge protection by zoneDown conductor
The conductor that carries lightning current from the air termination to the earth termination. At least two on any attached system, spaced 10 to 20 m by class.
Facade and down conductor systemsEarth electrode
A conductive part in electrical contact with the soil, directly or through concrete: rod, strip, plate, ring or foundation electrode.
Earth electrodesEarth enhancing compound
A conductive backfill used around an electrode in high-resistivity soil. IS 3043:2026 limits it to resistivity above 3000 Ω·m and to lightning protection use.
Earth enhancing compoundsEarth fault loop impedance (Zs)
The impedance of the path a fault current takes from the source, through the line conductor and the protective conductor, back to the source. It decides whether the protective device trips in time.
Loop impedance calculatorEarth potential rise (EPR)
The voltage an earthing system rises to, relative to remote earth, when fault or lightning current flows into it.
Substation grid earthingEarth termination system
The part of a lightning protection system that disperses the current into the ground. Type A is individual electrodes at each down conductor. Type B is a ring or foundation electrode.
Ring earth electrodeEarthing conductor
The conductor joining the main earthing terminal to the earth electrode. At least 6 mm² copper, or 16 mm² copper where a lightning protection system is connected. Aluminium is not permitted.
Earthing strips, tapes and cablesEquipotential bonding
Connecting exposed and extraneous conductive parts so they sit at substantially the same potential. Required in every building by the CEA Regulations.
Equipotential bondingExothermic welding
A permanent molecular joint between conductors made by a controlled reaction in a mould. It does not loosen or corrode like a mechanical joint.
Exothermic weldingExposed conductive part
A metal part of equipment that can be touched and is not normally live but can become live under a fault, such as a motor frame or panel enclosure.
Equipotential bondingExtraneous conductive part
A metal part that is not part of the electrical installation but can introduce a potential, such as a water pipe, structural steel or a cable tray.
Bonding productsFoundation earth electrode
A conductor embedded in the concrete of a building foundation, bonded to the reinforcement at least every 2 m, forming a closed ring.
Foundation earth electrodeGlobal earthing system (GES)
Local earthing systems interconnected closely enough that no dangerous touch voltage appears between them. Required where an HV substation sits within the premises.
Global earthing systemImpulse current (Iimp)
The 10/350 µs test current of a Type 1 surge protective device. It represents a share of a direct lightning strike.
Type 1 lightning current arrestersIsolated LPS
A lightning protection system whose air termination and down conductors are kept clear of the structure, so that no lightning current flows through it.
Isolated lightning protectionIsolating spark gap
A component that keeps two metal parts electrically apart in normal service and bonds them during a lightning strike.
Isolating spark gapsLEMP
Lightning electromagnetic impulse: the conducted surges and radiated fields from a strike that damage electrical and electronic systems.
How LEMP damages systemsLightning protection level (LPL)
One of four sets of lightning current values, I to IV. Each level maps to the class of system with the same number. LPL I assumes a 200 kA first stroke.
Standards & ComplianceLightning protection system (LPS)
The complete system that protects a structure from physical damage by lightning: an external system and an internal system of bonding and separation.
Lightning ProtectionLightning protection zone (LPZ)
A zone in which the lightning electromagnetic environment is defined. Surge protective devices are fitted where a line crosses from one zone to the next.
Lightning protection zonesMain earthing terminal (MET)
The terminal or bar to which protective conductors, bonding conductors and the earthing conductor of a building are connected.
Earth bars and terminalsMesh method
Placing air termination conductors as a grid over a flat surface. Mesh size runs from 5 m × 5 m for Class I to 20 m × 20 m for Class IV.
Mesh method on industrial roofsNatural component
A conductive part of the structure, such as reinforcement, a steel frame or a metal roof, that is used as part of the lightning protection system.
Natural componentsNominal discharge current (In)
The 8/20 µs test current of a Type 2 surge protective device.
Type 2 SPDsPE conductor
Protective earthing conductor. It connects exposed conductive parts to the main earthing terminal so that a fault is cleared and touch voltage is limited. Mandatory under the CEA Regulations.
Earthing conductorsPEN conductor
A conductor that combines the protective and neutral functions. It is permitted only upstream of the origin of an installation.
Power ProtectionProtection angle method
A way of placing air terminals on simple shapes. The angle falls as height rises and the method stops at the rolling sphere radius for the class.
Protection angle or rolling sphereResidual current device (RCD)
A device that disconnects a circuit when the current to earth exceeds its rating. 30 mA or less for domestic installations.
Power ProtectionRolling sphere method
The general method for placing air terminals. A sphere of 20, 30, 45 or 60 m radius is rolled over the structure. Anywhere it touches needs protection.
Rolling sphere: a practical guideSeparation distance (s)
The clearance needed between lightning protection conductors and other metal or electrical parts to prevent dangerous sparking.
How to calculate separation distanceSide flash
A discharge from a lightning conductor to a nearby metal part or person when the separation distance is too small. Also a strike to the side of a tall structure.
Side flash explainedSoil resistivity
The resistance of a unit volume of soil, in Ω·m. It is measured by the Wenner method in the dry season before an earthing system is designed.
Earth test instrumentsStep voltage
The voltage between two points on the ground one metre apart during a fault or strike.
Step and touch voltage controlSurge protective device (SPD)
A device that limits transient overvoltage and diverts surge current. Type 1 handles lightning current, Type 2 handles induced and switching surges, Type 3 protects at the equipment.
Surge protection devicesTest joint
A joint on each down conductor near the earth connection that can be opened with a tool to measure the earth electrode.
Test joints and inspection housingsTN-S system
A system with separate neutral and protective conductors throughout. The preferred arrangement for industrial and commercial installations.
Power ProtectionTouch voltage
The voltage between a metal part and the ground a person stands on while touching it during a fault.
Step and touch voltage controlType A earth electrode
Horizontal or vertical electrodes installed outside the structure at each down conductor, not forming a ring. At least two in total.
Rod earthingType B earth electrode
A ring conductor around the structure in contact with the soil for at least 80 % of its length, or a foundation earth electrode.
Ring earth electrodeVoltage protection level (Up)
The maximum voltage a surge protective device lets through. It must be below the impulse withstand voltage of the equipment, with margin for the lead length.
SPD SelectorSend it to us.
We will explain it in the context of your project and add it to this glossary.