IS 3043:2026 published: Earthing, Code of Practice (third revision)
The earthing code has been rewritten and aligned with the CEA Regulations 2023, the National Electrical Code 2023, IS 732:2019 and IS/IEC 61936-1. It supersedes IS 3043:2018.
What changed
- Separate “dedicated” or “clean” earth electrodes are listed as practices that shall not be followed. One interconnected, meshed network is required.
- For low-voltage installations there is no minimum electrode resistance. Protection is proven by loop impedance and disconnection time.
- Earth enhancing compounds are limited to soil above 3000 Ω·m and to lightning protection use, and barred below 200 Ω·m.
- New bonding resistance limits for substations: 0.1 mΩ per joint, 2.5 mΩ between parts within reach, 10 mΩ between any two items.
- New sections on foundation electrodes, global earthing systems, GIS, medical locations, solar PV and data centres.
What it means for your site
Sites built around separate pits for neutral, body, UPS and instrumentation no longer match the code. Review the earthing layout, interconnect the electrodes and add loop impedance and continuity tests to the periodic test plan.