The standards behind every LPES design, and what each one asks of your site.

Lightning protection, earthing and surge protection are governed by a stack of regulations and standards that refer to one another. This page sets out which document governs what, the values engineers use most, and the LPES solution and product family each one leads to.

4.Classes of lightning protection system, I to IV, set by the risk assessment
0.4 sMaximum disconnection time on a 230 V final circuit in a TN system
2.Separate and distinct earth connections for every transformer and generator neutral
1 yrInterval for earth resistance testing of a supplier’s or HV consumer’s earthing system
Order of authority

Which document wins when two disagree.

In India the hierarchy is set by the CEA Regulations themselves. An LPES design basis always states it in this order.

LevelAuthorityDocumentsHow it applies
1LawElectricity Act 2003 and the CEA (Measures relating to Safety and Electric Supply) Regulations 2023Mandatory. Where a regulation and a standard differ, the regulation prevails (Regulation 14).
2Indian Standards and codesIS 3043:2026, IS 732:2019, IS/IEC 62305, IS/IEC 61936-1, National Electrical Code (SP 30:2023), National Building CodeMade binding through Regulation 14, which requires the relevant standards to be followed.
3International standardsIEC 62305:2024, IEC 62561 series, IEC 61643 series, IEC 60364, IEEE 80Apply where no Indian Standard exists, in the order IEC, then IEEE, then European Norms. They are also the basis for export projects.
4Project specificationOwner, consultant and insurer requirementsMay be stricter than the standards. Never weaker.
The standards map

Which document governs which part of the system.

Choose a pillar. Each row names the document, what it controls, and where LPES applies it.

DocumentWhat it governsLPES solution and product
IEC 62305-1:2024General principles
Lightning current parameters, the four lightning protection levels and the sources of damage S1 to S4.
Lightning Protection
IEC 62305-2:2024Risk management
Risk R compared with a tolerable risk of 1 in 100,000 per year, and the frequency of damage F for internal systems. The result fixes the class of system and the SPD level.
Lightning Risk Assessment
IEC 62305-3:2024Physical damage and life hazard
Design of the external system: air termination, down conductors, earth termination, bonding, separation distance, inspection.
Flat roof LPSIsolated LPSAir termination
IEC 62305-4:2024Electrical and electronic systems
Protection against the lightning electromagnetic impulse: zones, bonding network, shielding, coordinated SPDs.
Surge protection by zone
IEC 62561-1 to -8Lightning protection system components
Product tests: -1 connection components, -2 conductors and earth electrodes, -3 isolating spark gaps, -4 conductor fasteners, -5 inspection housings, -6 strike counters, -7 earth enhancing compounds, -8 components for isolated systems.
Connection componentsLPS conductorsStrike counters
IS/IEC 62305Indian adoption
The Indian Standard route to the same requirements. Check which edition your project specification cites.
Standards updates
DocumentWhat it governsLPES solution and product
IS 3043:2026Earthing: code of practice (third revision)
System earthing, protective earthing and bonding for land-based installations. Disconnection times, conductor sizing, electrode sizes and materials, substation earthing, testing.
Global earthing systemEarthing conductorsEarth electrodes
IS 732:2019Electrical wiring installations
Design and verification of installations up to 1000 V AC: shock protection, cable sizing, protective conductors, inspection and test.
Equipotential bondingEarth bars
IEEE 80Safety in AC substation grounding
Grid design for substations and switchyards: tolerable touch and step voltage, conductor sizing, grid resistance, mesh and step voltage.
Substation grid earthingEarth mats and grids
IS/IEC 61936-1Power installations above 1 kV AC
Earthing of high-voltage installations: earth potential rise, permissible touch voltage, global earthing system.
Substation protectionStep and touch control
IEC 60364-6Verification
Initial and periodic verification of low-voltage installations: continuity, insulation resistance, loop impedance, RCD tests.
Periodic inspection and testingEarth test instruments
DocumentWhat it governsLPES solution and product
IEC 61643-11SPDs for low-voltage power systems
Product requirements and tests for Type 1, Type 2 and Type 3 devices: impulse current, nominal discharge current, voltage protection level.
Type 1 arrestersType 1+2 combinedType 2 SPDs
IEC 61643-21SPDs for telecom and signalling networks
Devices for data, signal, measurement and control lines.
Data, signal and RF SPDs
IEC 61643-31 / -32SPDs for photovoltaic installations
Product standard and selection rules for the DC side of PV systems.
Rooftop solar protectionDC and PV SPDs
IEC 61643-12 / -22Selection and application
How to choose, coordinate and install SPDs on power and signal lines.
SPD Selector
IEC 60364-5-53Devices for protection and switching
Where SPDs are required in an installation and how they are connected, including lead length and back-up protection.
SPD assembliesCritical facilities
DocumentWhat it governsLPES solution and product
CEA Reg. 38(3)Lightning protection of buildings
Lightning protection to the relevant standards for multi-storeyed buildings above 15 m and for hospitals, hotels, airports, academic buildings, industrial installations, places with explosive or flammable material, stations and other public buildings.
Lightning ProtectionHazardous areas
CEA Reg. 43Connection with earth, 50 V to 650 V
Protective equipotential bonding in every building, two separate earth connections for equipment above 250 V and for every generator and transformer neutral, loop impedance tested so the protective device operates in time.
Equipotential bondingEarthing conductors
CEA Reg. 44Residual current device
Supply controlled by an RCD. Not more than 30 mA for domestic installations.
Power Protection
CEA Reg. 50Connection with earth above 650 V
An earth mat that limits touch and step potential and earth potential rise. Resistance tested on a dry day in the dry season at least once a year, with records kept.
Substation grid earthingInspection and testing
CEA Reg. 77Protection against lightning
Overhead lines, substations and generating stations exposed to lightning must divert surges to earth. Arrester earth leads short, direct and without bends.
Substation protection
CEA Reg. 121Solar PV
Earthing of all array structures, lightning and overvoltage protection, and an SPD in every combiner box.
Rooftop solar protectionPV string combiner boxes
CEA Reg. 124EV charging stations
A lightning protection system to the relevant standards and earth continuity monitoring.
Power Protection
The numbers engineers use most

Key values, with the clause they come from.

Quoted individually for reference. Always confirm against the licensed standard before a value goes into a design.

Class of LPSRolling sphere radiusMesh sizeDown conductor spacingFactor kiPeak current
Class I20 m5 × 5 m10 m0.08200 kA
Class II30 m10 × 10 m10 m0.06150 kA
Class III45 m15 × 15 m15 m0.04100 kA
Class IV60 m20 × 20 m20 m0.04100 kA

IEC 62305-3:2024, Tables 2, 5 and 11. The class comes from the IEC 62305-2 risk assessment and is never chosen by preference. Apply these values to your building

ElementMinimumReferenceProduct family
Air termination and down conductor50 mm² in copper, aluminium, galvanised or stainless steel (tape, round or stranded)IEC 62305-3, Table 7LPS conductors
Earth electrode in soilCopper 50 mm², copper-bonded steel rod 14 mm, galvanised strip 90 mm², stainless rod 16 mmIS 3043:2026, Table 26Earth electrodes
Bonding bar to earth terminationCopper 16 mm², aluminium 25 mm², steel 50 mm²IEC 62305-3, Table 9Earth bars
Earthing conductor, main earthing terminal to electrodeAt least 6 mm² copper or 50 mm² steel. 16 mm² copper where a lightning protection system is connected. Aluminium is not permitted.IS 3043:2026, 7.3.3Earthing strips and cables
Main protective bonding conductorHalf the largest protective conductor, at least 6 mm² copper, need not exceed 25 mm² copperIS 3043:2026, 7.3Equipotential bonding
AluminiumNever in soil and never in concreteIEC 62305-3, Table 6Corrosion protection
StructureVisual inspectionComplete inspection with electrical tests
Normal structuresEvery yearEvery 3 years
Severe weather or high mechanical stressEvery 6 monthsEvery year
Structures with a risk of explosionEvery yearEvery year
Sensitive internal systems, offices, places of assemblyEvery yearEvery year (complete inspection)

IEC 62305-3:2024, Annex D.7. Also inspect after any alteration, repair or known strike. In India, earth resistance of HV and supplier earthing systems is tested at least once a year (CEA Regulations 43 and 50). Set up periodic inspection and testing

Nominal voltage to earth (AC)TN systemTT system
50 to 120 V0.8 s0.3 s
120 to 230 V0.4 s0.2 s
230 to 400 V0.2 s0.07 s
Above 400 V0.1 s0.04 s

IS 3043:2026, Table 1, for final circuits. Distribution circuits: 5 s in TN and 1 s in TT. Where protective equipotential bonding is not proven, the TT times apply to every circuit. In low-voltage installations the standard sets no minimum electrode resistance: protection rests on loop impedance and automatic disconnection. Check a loop impedance

Five things the standards say that sites often get wrong

Common practice against the published requirement.

Common practiceWhat the standard saysGo to
Separate “dedicated” earth pits for each transformer, panel, lift or UPSOne interconnected, meshed earthing and bonding network. IS 3043:2026 lists separate and isolated electrodes among practices that shall not be followed.Global earthing system
“Double earthing” means two pits in the groundIt means two separate connections to the earthing system. The CEA Regulations require two distinct connections, not two electrodes.Equipotential bonding
A low earth resistance value proves the installation is safeIn low voltage, safety rests on loop impedance and disconnection time. In high voltage, it rests on touch and step voltage.Step and touch voltage control
A lightning protection system protects the electronics insideAn external system with bonding SPDs prevents dangerous sparking only. Electronics need coordinated SPDs to IEC 62305-4.Surge protection by zone
Earth enhancing compound improves any earthIS 3043:2026 limits it to resistivity above 3000 Ω·m, for lightning protection, and bars it below 200 Ω·m.Earth enhancing compounds
What “complies” means

Tested to, built to, complies with.

LPES products are built and tested to the product standards that apply to them, and LPES designs are prepared to comply with the installation standards named in the design basis. These are different claims and we keep them apart.

Product standards such as IEC 62561 and IEC 61643 define type tests. A product can be tested to them.

Installation standards and codes of practice such as IEC 62305-3 and IS 3043 define how a system is designed, installed and verified. An installation complies with them. It is not “certified to” them.

Compliance of an installation is demonstrated by inspection and test by competent persons and accepted by the Electrical Inspector or the authority having jurisdiction. See LPES certifications and approvals

LPES lightning protection, earthing and surge protection product portfolio
Questions on compliance

Short answers, with the clause.

Is lightning protection mandatory in India?

For many buildings, yes. Regulation 38(3) of the CEA Regulations 2023 requires lightning protection to the relevant standards for multi-storeyed buildings above 15 m and for a list of premises that includes hospitals, hotels, airports, academic buildings, industrial installations and places holding explosive or flammable material. For other structures the need is decided by a risk assessment to IEC 62305-2. Assess your structure

Which standard does lightning protection follow in India?

The CEA Regulations refer to the relevant Indian Standards, the National Electrical Code and the National Building Code. In practice that means IS/IEC 62305, with components to the IEC 62561 series. Lightning protection solutions

Is IS 3043 mandatory?

The foreword to IS 3043:2026 states that the Electricity Act 2003, read with Regulation 14 of the CEA Regulations 2023, makes compliance with Indian Standards, including IS 3043, mandatory. Earthing solutions

Are surge protective devices mandatory?

The CEA Regulations require them explicitly for solar PV combiner boxes (Regulation 121) and require surge diversion for lines, substations and generating stations (Regulation 77). Elsewhere the need follows from the IEC 62305-2 risk assessment and IEC 60364. Where a lightning protection system is installed, Type 1 SPDs at the service entrance are required by IEC 62305. Select an SPD

What earth resistance must a lightning protection earth achieve?

IEC 62305-3 recommends below 10 Ω where possible, measured at low frequency. For a Type A arrangement the minimum electrode length may be waived when each electrode is below 10 Ω. Rod earthing (Type A)

How long must test records be kept?

Suppliers must keep earth test records for at least two years and make them available to the Electrical Inspector (Regulation 43). We recommend keeping every record for the life of the installation. Monitoring and record

Check your site against the standards

Request a compliance review.

We review drawings, test records and the installed system against the CEA Regulations, IS 3043 and IS/IEC 62305, and report each item as complies, does not comply or not demonstrated.

This page summarises published requirements for guidance. It does not replace the licensed standards, the Gazette text of the regulations or later amendments, and it is not a certificate of compliance. Design and verification must be carried out by competent persons.